More Information
Manufacturer SCHNEIDER Electric
Manufacturer code LC1K1210P5
Order Unit Pce
Range TeSys
Product Name TeSys K
Product or component type Contactor
Device short name LC1K
Contactor application Resistive load; Motor control
Utilisation category

AC-1
AC-3
AC-4

Power pole contact composition 3 NO
Device application Control
Poles description 3P
[uc] Control Circuit Voltage 230 V AC 50 Hz
[Ue] rated operational voltage Power circuit: 690 V AC 50 Hz; Signalling circuit: 690 V AC 50 Hz
[Ie] rated operational current

12 A at <= 440 V AC AC-3 for power circuit
20 A (at <50 °C) at <= 440 V AC AC-1 for power circuit
16 A (at <70 °C) at 690 V AC AC-1 for power circuit

Motor power kW

3 kW at 220...230 V AC 50 Hz AC-3
5.5 kW at 380...415 V AC 50 Hz AC-3
5.5 kW at 440 V AC 50 Hz AC-3
4 kW at 480 V AC 50 Hz AC-3
4 kW at 500...600 V AC 50 Hz AC-3
4 kW at 660...690 V AC 50 Hz AC-3
2.2 kW at 400 V AC 50 Hz AC-4

Control circuit type AC at 50 Hz
Product Weight 0.18 kg
Average impedance 3 mOhm - Ith 20 A 50 Hz for power circuit
[Ui] Rated insulation voltage Power circuit: 690 V conforming to IEC 60947-4-1; Power circuit: 600 V conforming to UL 60947-4-1; Power circuit: 600 V conforming to CSA C22.2 No 60947-4-1
[Uimp] Rated impulse withstand voltage 8 kV
Mounting support Plate; Rail
Auxiliary contact composition 1 NO
[Ith] conventional free air thermal current 20 A (at 50 °C) for power circuit; 10 A (at 50 °C) for signalling circuit
Mechanical durability 10 Mcycles
Electrical durability 1.3 Mcycles 12 A AC-3 at Ue <= 440 V; 0.3 Mcycles 20 A AC-1 at Ue <= 440 V
Connections - terminals

Screw clamp terminals 1 cable(s) 1.5…4 mm²solid
Screw clamp terminals 1 cable(s) 0.75…4 mm²flexible without cable end
Screw clamp terminals 1 cable(s) 0.34…2.5 mm²flexible with cable end
Screw clamp terminals 2 cable(s) 1.5…4 mm²solid
Screw clamp terminals 2 cable(s) 0.75…4 mm²flexible without cable end
Screw clamp terminals 2 cable(s) 0.34…1.5 mm²flexible with cable end

Tightening torque 1.3 N.m - on screw clamp terminals - with screwdriver Philips No 2; 1.3 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm; 1.3 N.m - on screw clamp terminals - with screwdriver pozidriv No 2
Operating time

10...20 ms coil de-energisation and NO opening
10...20 ms coil energisation and NO closing

Safety reliability level

B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1
B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1

Standards

EN/IEC 60947-4-1
IEC 60947-4-1
UL 60947-4-1
CSA C22.2 No 60947-4-1
BS 5424
NF C 63-110
VDE 0660

Product certifications

UL
CSA
CCC
EAC
KC
LROS (Lloyds register of shipping)
DNV-GL
RINA
BV
UKCA

Irms rated making capacity

110 A AC for signalling circuit conforming to IEC 60947
144 A AC for power circuit conforming to NF C 63-110
144 A AC for power circuit conforming to IEC 60947

Rated breaking capacity 110 A at 440 V conforming to IEC 60947; 80 A at 500 V conforming to IEC 60947; 70 A at 660...690 V conforming to IEC 60947
Operating altitude 2000 m without derating
Ambient air temperature for storage -50…80 °C
Minimum switching current 5 mA for signalling circuit
Minimum switching voltage 17 V for signalling circuit
Height 58 mm
Width 45 mm
Depth 57 mm
Associated fuse rating

25 A gG at <= 440 V for power circuit
25 A aM for power circuit
10 A gG for signalling circuit conforming to IEC 60947
10 A gG for signalling circuit conforming to VDE 0660

Protective treatment TC conforming to IEC 60068; TC conforming to DIN 50016
IP degree of protection

IP20 conforming to VDE 0106

Flame retardance V1 conforming to UL 94; Requirement 2 conforming to NF F 16-101; Requirement 2 conforming to NF F 16-102
Mechanical robustness Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6; Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Maximum operating rate

3600 cyc/h

Control circuit voltage limits

Operational: 0.8...1.15 Uc (at <50 °C)
Drop-out: 0.2...0.75 Uc (at <50 °C)

Inrush power in VA

30 VA (at 20 °C)

Hold-in power consumption in VA

4.5 VA (at 20 °C)

Heat dissipation 1.3 W
Auxiliary contacts type

Type instantaneous 1 NO

Signalling circuit frequency <= 400 Hz
Non Overlap Distance 0.5 mm
Overvoltage Category CAT III