SCHNEIDER Electric - TeSys D contactor 3P 9A AC-3 440V, aux 1NO+1NC, 24V 50Hz

Lei 88.00 Lei 73.95
In stock
Only 3 left
SKU
LC1D09B5
Free shipping for orders over 500 lei
Free shipping applies to cities without additional kilometers or heavy/high volume products
Write Your Own Review
You're reviewing:SCHNEIDER Electric - TeSys D contactor 3P 9A AC-3 440V, aux 1NO+1NC, 24V 50Hz
More Information
Manufacturer SCHNEIDER Electric
Manufacturer code LC1D09B5
Order Unit Pce
Range TeSys
Product Name TeSys D; TeSys Deca
Product or component type Contactor
Utilisation category

AC-1
AC-3
AC-4
AC-3e

Power pole contact composition 3 NO
Poles description 3P
[uc] Control Circuit Voltage 24 V c.a. 50 Hz
[Ue] rated operational voltage Electrical circuit <= 690 V a.c. 50 Hz; Electrical circuit <= 300 V d.c.
[Ie] rated operational current

9 A 60 ° C) at <= 440 V AC-3 for electrical circuit
25 A 60 ° C) at <= 440 V AC-1 for electrical circuit
9 A 60 ° C) at <= 440 V AC-3e for electrical circuit

Motor power kW

2,2 kW at 220...230 V c.a. 50 Hz (AC-3)
4 kW at 380...400 V c.a. 50 Hz (AC-3)
4 kW at 415...440 V c.a. 50 Hz (AC-3)
5,5 kW at 500 V c.a. 50 Hz (AC-3)
5,5 kW at 660...690 V c.a. 50 Hz (AC-3)
2,2 kW at 400 V c.a. 50 Hz (AC-4)
3 kW at 220...230 V c.a. 50/60 Hz (AC-3e)
5,5 kW at 380...400 V c.a. 50/60 Hz (AC-3e)
5,5 kW at 415...440 V c.a. 50/60 Hz (AC-3e)
7,5 kW at 500 V c.a. 50/60 Hz (AC-3e)
7,5 kW at 660...690 V c.a. 50/60 Hz (AC-3e)

Control circuit type C.a. at 50 Hz
Product Weight 0,32 kg
Average impedance 2,5 mOhm - Ith 25 A 50 Hz for electrical circuit
[Ui] Rated insulation voltage 690 V electrical circuit according to IEC 60947-4-1; 600 V CSA certified electrical circuit; UL certified 600 V electrical circuit; CSA certified 600 V signaling circuit
[Uimp] Rated impulse withstand voltage 6 kV according to SR EN 60947-2
Power dissipation per pole 0,2 W AC-3; 1,56 W AC-1; 0,2 W AC-3e
Front cover Cu
Mounting support Rail, Plate
Auxiliary contact composition 1 NO + 1 NC
[Ith] conventional free air thermal current 25 A at <60 ° C for electrical circuit; 10 A at <60 ° C for signaling circuit
Mechanical durability 15 Mcycles
Electrical durability 2 Mcycles 9 A AC-3 at Ue <= 440 V;0,6 Mcycles 25 A AC-1 at Ue <= 440 V; 2 Mcycles 9 A AC-3e at Ue <= 440 V
Connections - terminals

Electrical circuit terminal with screw 1 cable (s) 1… 4 mm²flexible without
Electrical circuit terminals with screw 2 cable (s) 1… 4 mm²flexible without
Electrical circuit terminal with screw 1 cable (s) 1… 4 mm²flexible with
Electrical circuit terminals with screw 2 cable (s) 1… 2.5 mm²flexible with
Electrical circuit terminal with screw 1 cable (s) 1… 4 mm²solid without
Electrical circuit terminal with screw 2 cable (s) 1… 4 mm²solid without
Terminal control circuit with screw 1 cable (s) 1… 4 mm²flexible without
Terminal control circuit with screw 2 cable (s) 1… 4 mm²flexible without
Terminal control circuit with screw 1 cable (s) 1… 4 mm²flexible with
Terminal control circuit with screw 2 cable (s) 1… 2.5 mm²flexible with
Terminal control circuit with screw 1 cable (s) 1… 4 mm²solid without
Terminal control circuit with screw 2 cable (s) 1… 4 mm²solid without

Tightening torque 1.7 N.m electrical circuit - screw terminals on - with flat screwdriver Ø 6 mm; 1.7 N.m electrical circuit - on screw terminals - with Philips screwdriver Nr. 2
Operating time

12 ... 22 ms closing
4 ... 19 ms opening

Standards

IEC 60947-4-1
EN/IEC 60947-1
SR EN 60947-5-1
SR EN 60947-5-1
UL 60947-4-1
CSA C22.2 No 60947-4-1

Product certifications

UL
CSA
CCC
EAC
KC
LROS (Lloyds register of shipping)
DNV-GL
RINA
BV
UKCA

Irms rated making capacity

250 A at 440 V for electrical circuit in accordance with SR EN 60947
140 A c.a. for signaling circuit in accordance with SR EN 60947-5-1
250 A c.c. for signaling circuit in accordance with SR EN 60947-5-1

Rated breaking capacity 250 A at 440 V for electrical circuit in accordance with SR EN 60947
Pollution degree 3
Operating altitude 0...3000 m
Ambient air temperature for storage -60…80 °C
Ambient air temperature for operation -40… 60 ° C; 60… 70 ° C with downgrading
Minimum switching current 5 mA for signaling circuit
Minimum switching voltage 17 V for signaling circuit
Height 77 mm
Width 45 mm
Depth 86 mm
Associated fuse rating

10 A gG for signaling circuit in accordance with SR EN 60947-5-1
25 A gG at <= 690 V type 1 coordination for electrical circuit
20 A gG at <= 690 V type 2 coordination for electrical circuit

Protective treatment TH conforming to IEC 60068-2-30
IP degree of protection

IP20 frontal conforming to SR EN 60529

Maximum operating rate

3600 cic/h at <60 °C

Control circuit voltage limits

0.3 ... 0.6 Uc -40… 70 ° C elimination c.a. 50 Hz
0.8 ... 1.1 Uc -40… 60 ° C operational c.a. 50 Hz
1 ... 1.1 Uc 60… 70 ° C operational c.a. 50 Hz

Hold-in power consumption in VA

70 VA 50 Hz 0,75 20 °C)

Heat dissipation 2…3 W at 50 Hz
Auxiliary contacts type

Mechanical coupling type 1 NO + 1 NC according to SR EN 60947-5-1
contact type in mirror 1 NC according to IEC 60947-4-1

Signalling circuit frequency 25...400 Hz
Non-overlap time

1.5 ms on de-energisation no overlap betweenNO and NC contacts
1.5 ms on energisation no overlap between NO and NC contacts

Overvoltage Category CAT III

 