We use cookies to make your experience better. To comply with the new e-Privacy directive, we need to ask for your consent to set the cookies. Learn more.
SCHNEIDER Electric - Motor circuit breaker, TeSys deca GV2, 3P, 6-10 A, thermal magnetic, screw clamp terminals
Lei 169.00
Lei 142.02
in supplier stock
SKU
GV2ME14AP
Free shipping for orders over 500 lei
Free shipping applies to cities without additional kilometers or heavy/high volume products
Write Your Own Review
Manufacturer | SCHNEIDER Electric |
---|---|
Manufacturer code | GV2ME14AP |
Order Unit | Pce |
Range | TeSys GV2 |
Product Name | TeSys GV2; TeSys Deca |
Product or component type | Circuit breaker |
Device short name | GV2ME |
Poles description | 3P |
[In] rated current | 10 A |
[Ie] rated operational current | 690 V c.a. 50 Hz conform SR EN 60947-2 |
Motor power kW | 3…4 kW at 400/415 V c.a. 50 Hz |
Magnetic tripping current | 138 A |
Network type | C.a. |
Trip unit technology | Thermo-magnetic |
Product Weight | 0,26 kg |
Breaking capacity | 100 kA Icu at 230/240 V a.c. 50 Hz according to SR EN 60947-2 |
Suitability for isolation | Yes conforming to IEC 60947-1 |
Network frequency | 50 Hz |
[Ui] Rated insulation voltage | 690 V c.a. 50 Hz conform SR EN 60947-2 |
[Uimp] Rated impulse withstand voltage | 6 kV conformitate cu SR EN 60947-2 |
Power dissipation per pole | 2,5 W |
Control type | Button |
Mounting mode | Symmetrical DIN rail, 35 mm clamped; Screw panel (with flat adapter) |
[Ith] conventional free air thermal current | 10 A conforming to IEC 60947-4-1 |
Mechanical durability | 100000 cic |
Electrical durability | 100000 cycles for AC-3 at 440 V |
Tightening torque | 1.7 N.m on screw terminals |
Standards | SR EN 60947-2 |
Product certifications | IECEE CB Scheme |
Operating altitude | 2000 m |
Ambient air temperature for storage | -40…80 °C |
Ambient air temperature for operation | -20…60 °C |
Height | 89 mm |
Width | 45 mm |
Depth | 78,5 mm |
Thermal protection adjustment range | 6…10 A |
Phase failure sensitivity | Yes conforming to IEC 60947-4-1 |
Protective treatment | TH |
IP degree of protection | IP20 conform SR EN 60529 |
Maximum operating rate | 25 cic/h |